Santej, Ahmedabad, Gujarat, India CE-Marked Transformers for Export
Serving OEMs & Projects Worldwide

60hz 300 Amps Active Filter Panel for Harmonics Filtering AHF Panel

Product Description

Product Introduction
Product Name: 60hz 300 Amps Active Filter Panel For Harmonics Filtering AHF panel

SFR-APF which intergrated with HMI control system uses an efficient power electronics topology and advanced all-digital control technology to dynamically filter harmonics.

Active Filter Panel Interior View
Active Filter Panel Module View
AHF Free Standing Enclosure
Active Filter Component Assembly
Working Principle
Active Harmonic Filter Operation Circuit Diagram
Harmonic Waveform Compensation Diagram
Application

SFR-APF can be widely used in the following industrial fields (steel industry, metallurgy industry, mining industry, new energy industry, automotive industry), municipal field (water treatment industry, telecommunications industry, research institutes), commercial field (hospital, bank, shopping mall , schools, computer rooms, computer centers), rail transportation (electrified railways, subways).

Data Center Harmonic Solution
Data Center
Hospital Power Quality Mitigation
Hospital
Industrial Harmonic Filtering
Industry
Technical Parameters
Input
System voltage Line voltage 400V
System voltage range ±15%
Frequency 50Hz ±5%
Output and installation
Capacity specification 300A
Module type Free Standing Panel
Incoming way Upper incoming/Back incoming
Performance
Harmonics filtering rate ≥90% (Within the range of the ordered capacity, and the load harmonic content is higher than 30% of the ordered capacity)
Harmonics filtering range 2nd ~51st harmonics (If you need to control the harmonic order of more than 25 times, you should write in the contract)
Full response time ≤5ms
Instantaneous response time ≤100us
Dynamic current 1.2 times the filter rated capacity output, 1min
Protection
Overload protection Automatic current limit at 100% rated output
Other protection Over-voltage protection, under-voltage protection, over-temperature protection, over-current protection
Operation mode
Stand-alone operation Support
Parallel operation Conventionally support 8 sets, special requirements can be customized
Display and operation
Status display Power / Operation / Fault LED indication
Module operation Start/Stop/Restart
HMI (Optional) Optional 7” (Hole size 215×152mm)  10” (Hole size 261×180mm)
Communication
(RS485 interface)
1 loop Modbus-RTU protocol external communication interface, Users can have access to the background system through this interface or HMI port
Environment condition
IP level IP20 (customized)
Operating environment temperature -25℃ ~ 40℃
Storage/ transport temperature -25℃ ~ 55℃
Work humidity Relative humidity 5~95%, no condensation
Altitude 1000m and below (above 1000m, Every additional 100m / 1% derating)
Standard IEEE519
Standard Compliance
Active Filter Compliance Certificate
  • IEEE519
  • 2014/30/EU 2014/35/EU
  • EN 61000-6-2:2005+AC:2005
  • EN 61000-6-4:2007+A1:2011
  • EN 50178:1997
Project Reference
On-Site Active Harmonic Filter Installation Project
Company Profile
Factory Facility Overview
Manufacturing Line
Testing and Assembly Area
Factory Production View
Quality Control Lab
Contact Us
Contact Information
Customer Service Inquiry
Frequently Asked Questions (FAQ)
What is the harmonic mitigation efficiency of this Active Filter Panel?
The SFR-APF achieves a harmonics filtering rate of ≥90% within the ordered capacity range, given that the load harmonic content exceeds 30% of the unit's rated capacity.
What harmonic range does the SFR-APF cover?
The system dynamically compensates from the 2nd to the 51st harmonic order. Specialized control targeting orders above the 25th can also be configured upon request.
How fast is the dynamic response time?
The panel delivers an instantaneous response time of ≤100 microseconds and achieves complete harmonic compensation in ≤5 milliseconds.
Can multiple active harmonic filter units run in parallel?
Yes, standard configurations support parallel operation of up to 8 units, with custom expansion schemes available for larger industrial demands.
What system protections are built into the panel?
Comprehensive safety functions include automatic current limiting at 100% rated output, over-voltage, under-voltage, over-temperature, and over-current protection.
Which communication protocols are supported for remote management?
It features an RS485 interface with standard Modbus-RTU protocol support, facilitating direct communication with SCADA and building management systems via HMI or back-end network ports.