1 / 5
SFR-APF which intergrated with HMI control system uses an efficient power electronics topology and advanced all-digital control technology to dynamically filter harmonics.
SFR-APF can be widely used in the following industrial fields (steel industry, metallurgy industry, mining industry, new energy industry, automotive industry), municipal field (water treatment industry, telecommunications industry, research institutes), commercial field (hospital, bank, shopping mall , schools, computer rooms, computer centers), rail transportation (electrified railways, subways).
| Input | |
| System voltage | Line voltage 400V |
| System voltage range | ±15% |
| Frequency | 50Hz ±5% |
| Output and installation | |
| Capacity specification | 300A |
| Module type | Free Standing Panel |
| Incoming way | Upper incoming/Back incoming |
| Performance | |
| Harmonics filtering rate | ≥90% (Within the range of the ordered capacity, and the load harmonic content is higher than 30% of the ordered capacity) |
| Harmonics filtering range | 2nd ~51st harmonics (If you need to control the harmonic order of more than 25 times, you should write in the contract) |
| Full response time | ≤5ms |
| Instantaneous response time | ≤100us |
| Dynamic current | 1.2 times the filter rated capacity output, 1min |
| Protection | |
| Overload protection | Automatic current limit at 100% rated output |
| Other protection | Over-voltage protection, under-voltage protection, over-temperature protection, over-current protection |
| Operation mode | |
| Stand-alone operation | Support |
| Parallel operation | Conventionally support 8 sets, special requirements can be customized |
| Display and operation | |
| Status display | Power / Operation / Fault LED indication |
| Module operation | Start/Stop/Restart |
| HMI (Optional) | Optional 7” (Hole size 215×152mm) 10” (Hole size 261×180mm) |
| Communication (RS485 interface) |
1 loop Modbus-RTU protocol external communication interface, Users can have access to the background system through this interface or HMI port |
| Environment condition | |
| IP level | IP20 (customized) |
| Operating environment temperature | -25℃ ~ 40℃ |
| Storage/ transport temperature | -25℃ ~ 55℃ |
| Work humidity | Relative humidity 5~95%, no condensation |
| Altitude | 1000m and below (above 1000m, Every additional 100m / 1% derating) |
| Standard | IEEE519 |